Research Library · Idea
ICD/ICS 705 SCIF technical specification
Intelligence Community Directive 705, Sensitive Compartmented Information Facilities, and the standards and technical specification issued under it set the physical and technical security requirements for the facilities (SCIFs) where U.S. intelligence community elements process, store, use or discuss Sensitive Compartmented Information (SCI). The directive is a three-page policy issued under the National Security Act of 1947, Executive Order 12333 and Executive Order 13526. It requires all SCI to be handled in an accredited SCIF, requires every SCIF to meet uniform IC physical and technical security requirements, and rescinded Director of Central Intelligence Directive 6/9 and its manual and annexes. It assigns accreditation to IC element heads, who may delegate it to an Accrediting Official; sets rules for waivers for a documented mission need; makes SCIFs available for reciprocal use; and applies State Department Overseas Security Policy Board standards to SCIFs under Chief of Mission authority. 1 The NCSC's Technical Specifications cite the directive as dated 26 May 2010, alongside ICS 705-1 (physical and technical standards, 27 September 2010) and ICS 705-2 (accreditation and reciprocal use, 22 December 2016). 2
The Technical Specifications for Construction and Management of SCIFs, prepared by the National Counterintelligence and Security Center, give the detailed construction and operating requirements. Version 1.5 is dated 13 March 2020; version 1.5.1, dated 26 July 2021, changed Chapter 13 on Second Party integree and liaison spaces. 2 For SCIFs in the United States, alarm response must be 15 minutes for closed storage, and for open storage 15 minutes if the area is covered by security-in-depth or five minutes if it is not. Chapter 7 requires intrusion detection when a SCIF is unoccupied, compliance with UL 2050 and an Extent 3 installation, UL 639 motion sensors and UL 634 Level II high security switches, and an intrusion detection system kept separate from fire and other building systems with auto-reset disabled. False alarms may not exceed one per 30-day period per partition. Transmission lines leaving the SCIF must use FIPS-certified encryption, noted on the UL 2050 certificate. If line security, sensors or power fail, SCI-indoctrinated staff must occupy the SCIF, or a guard force must watch its perimeter, until the system is restored. 2
The directive's reach extends beyond the IC. In the NISPOM, 32 CFR 117.15(d), the cognizant security agency bases approval of a contractor's new intrusion detection system on ICD 705 and applicable IC standards, on UL 2050, or on its own written criteria. 3
Source · Intelligence Community Directive 705, Sensitive Compartmented Information Facilities (opens in a new tab) · Office of the Director of National Intelligence (archived copy, Internet Archive)
References
- Intelligence Community Directive 705, Sensitive Compartmented Information Facilities (opens in a new tab) · Office of the Director of National Intelligence (archived copy, Internet Archive) · May 26, 2010 · Three-page directive; effective date as cited in the Technical Specifications. ↩
- Technical Specifications for Construction and Management of Sensitive Compartmented Information Facilities, Version 1.5.1 (opens in a new tab) · National Counterintelligence and Security Center (archived copy, Internet Archive) · July 26, 2021 · Chapter 2 response times and Chapter 7 intrusion detection systems. ↩ ↩ ↩
- 32 CFR 117.15, Safeguarding classified information (opens in a new tab) · U.S. Government Publishing Office (GovInfo) · July 1, 2025 · Official annual edition, revised as of 1 July 2025; paragraph (d) covers intrusion detection systems. ↩
Research articles
- Building a SCIF: what ICD 705 and the IC Tech Spec require, and what is only reported about changes in 2025 and 2026 · Physical security
- Detect, assess, respond: intrusion alarms, monitoring stations and what a UL certificate promises · Physical security
See what connects to it on the map of ideas →

SecSIG